"A & C Exclusive Alarming Server Facet" Profile

 Description This Facet requires support for Alarms with multiple sub-states that identify different limit Conditions. This facet builds upon the A&C Alarm Server Facet. The term exclusive means only one sub-state can be active at a time. For example, a temperature exceeds the HighHigh limit the associated exclusive LevelAlarm will be in the HighHigh sub-state and not in the High sub-state. This Facet requires that a Server support at least one of the optional Alarm models: Limit, RateOfChange or Deviation.
 URI http://opcfoundation.org/UA-Profile/Server/ACExclusiveAlarming

This page lists the conformance units of the selected profile with their name and description.
Conformance units that are inherited via included Profiles are not listed by default. Use the following radio buttons to change this default behaviour.






Alarms and Conditions
Include  Name Opt.  Description  From Profile  Test Cases
A & C Exclusive Level Supports Exclusive Level Alarm type.   Open
A & C Exclusive Limit Supports Exclusive Limit Alarms. A Server that supports this must support at least one of the sub-types: Level, Deviation or RateofChange.   Open
A & C Exclusive Deviation Supports Exclusive Deviation Alarm type.   Open
A & C Exclusive RateOfChange Supports Exclusive RateOfChange Alarm type.   Open