View Issue Details

IDProjectCategoryView StatusLast Update
000323910000-009: Alarms and ConditionsSpecpublic2017-02-23 13:40
ReporterPaul Hunkar Assigned ToPaul Hunkar  
PrioritynormalSeverityminorReproducibilityhave not tried
Status closedResolutionfixed 
Product Version1.03 
Summary0003239: Silence from IEC62682
Description

IEC 62682 defines the concept of silence, this concepts should be integrated into the existing OPC UA information model, as an optional state machine - which would them make it available in all sub types and provide a much easier intgration of IEC 62682

TagsNo tags attached.
Commit Version
Fix Due Date

Relationships

related to 0003759 closedKarl Deiretsbacher 10000-007: Profiles Alarming: Silence State and Method 

Activities

Paul Hunkar

2016-07-21 04:10

developer   ~0007113

Added an optional two state statemachine to the AlarmConditiontype to allow the silence model. This state machine will also automatically silence on an acknowledge operation.

Jim Luth

2016-07-21 16:59

administrator   ~0007117

Fixed in Draft 1.04.03

Issue History

Date Modified Username Field Change
2015-12-03 01:54 Paul Hunkar New Issue
2015-12-03 01:54 Paul Hunkar Status new => assigned
2015-12-03 01:54 Paul Hunkar Assigned To => Paul Hunkar
2015-12-03 20:19 Paul Hunkar Summary Silence => Silence from IEC62682
2016-03-18 03:04 Paul Hunkar Description Updated
2016-07-21 04:10 Paul Hunkar Note Added: 0007113
2016-07-21 04:10 Paul Hunkar Status assigned => resolved
2016-07-21 04:10 Paul Hunkar Resolution open => fixed
2016-07-21 16:59 Jim Luth Note Added: 0007117
2016-07-21 16:59 Jim Luth Status resolved => closed
2016-07-21 16:59 Jim Luth Fixed in Version => 1.04
2017-02-23 13:40 Karl Deiretsbacher Relationship added related to 0003759