View Issue Details

IDProjectCategoryView StatusLast Update
000324110000-009: Alarms and ConditionsSpecpublic2017-03-23 15:07
ReporterPaul Hunkar Assigned ToPaul Hunkar  
PrioritynormalSeverityminorReproducibilityhave not tried
Status closedResolutionfixed 
Product Version1.03 
Summary0003241: Alarm System Diagnostics
Description

Define a structure (VariableType) that would provide the information that IEC 62682 is looking for as diagnostic information. It would be up to the server implementer to determine which objects include an instance of this variable (i.e. summary on the server level, summary on an Area, on an Object.....)

An initial list of diagnostic could include:
Both the peak and average alarm rates (10 minute intervals, 1 hour, 1 day)
total alarms
alarm flood summaries (duration, count of alarms, peak rate, number of floods)
Stale Alarms (in alarms for 24 hours or more)
Chattering Alarms (3 or more in a minute)

TagsNo tags attached.
Commit Version
Fix Due Date

Relationships

related to 0003760 closedKarl Deiretsbacher 10000-007: Profiles Alarm Metrics 

Activities

Paul Hunkar

2016-12-16 15:00

developer   ~0007620

Added alarm diagnostics, that include an object that can be used to collect diagnostics as needed.

Jim Luth

2017-03-23 15:07

administrator   ~0007956

Agreed to changes edited in Salzburg meeting.

Issue History

Date Modified Username Field Change
2015-12-03 20:34 Paul Hunkar New Issue
2015-12-03 20:34 Paul Hunkar Status new => assigned
2015-12-03 20:34 Paul Hunkar Assigned To => Paul Hunkar
2016-12-16 15:00 Paul Hunkar Note Added: 0007620
2016-12-16 15:00 Paul Hunkar Status assigned => resolved
2016-12-16 15:00 Paul Hunkar Resolution open => fixed
2017-02-23 14:01 Karl Deiretsbacher Relationship added related to 0003760
2017-03-23 15:07 Jim Luth Note Added: 0007956
2017-03-23 15:07 Jim Luth Status resolved => closed
2017-03-23 15:07 Jim Luth Fixed in Version => 1.04