Summary0003733: COM AE Mapping fActive to TransitionTime is not accurate.
Description

In COM AE fActive changes when an alarm goes active - it does not change when the alarm goes inactive. This means it cannot be directly mapped TransitionTime.

TagsNo tags attached.
Commit Version
Fix Due Date

Activities

Paul Hunkar

2017-02-13 02:23

developer   ~0007877

What section of the specification are you referring to? and do you have a suggestion as to what to change?

The COM mapping is just informative?

randyarmstrong

2017-03-14 17:36

administrator   ~0007919

The COM mapping is wrong and this is misleading because people read the spec and think that their existing alarm implementations can be mapped to AC as described by the spec. This is a problem even if it is informative.

Paul Hunkar

2017-03-16 05:40

developer   ~0007923

questions: This text is a description (it is informative) of what the Sample A&E wrapper and A&E proxy do, so has the code been changed, does it have a different mapping - if so what is it?

which section are you refereeing to the wrapper or proxy? (UA to A&E or A&E to UA) both are one directional if I remember correctly?

based on your comment - setting the transition time from FActive change is not incorrect (UA from A&E). Do we need to identify other items that could also set the transition time?

randyarmstrong

2017-03-16 09:17

administrator   ~0007924

This is a bug in the wrapper. No one is going to fix the wrapper code but we should not simply ignore the bug and move on. At a minimum there should be text in the appendix that flags the behavior as a known bug and points out that vendors developing their own wrappers cannot simply map the fActive to transition time and this information must come from non-COM AE sources.

Paul Hunkar

2017-03-24 03:14

developer   ~0007958

from meeting - theis about ftActiveTime, not ftTime and it is about the wrapper.

Paul Hunkar

2017-03-24 03:15

developer   ~0007959

Added text to indicate that it does not apply to some alarm type and it is about the transition to true for the active state.

Jim Luth

2017-04-25 20:11

administrator   ~0008007

Reviewed and agreed to close in 2017-04-11 telecon.

Issue History

Date Modified Username Field Change
2017-02-06 23:35 randyarmstrong New Issue
2017-02-13 02:23 Paul Hunkar Note Added: 0007877
2017-02-13 02:23 Paul Hunkar Assigned To => Paul Hunkar
2017-02-13 02:23 Paul Hunkar Status new => feedback
2017-03-14 17:36 randyarmstrong Note Added: 0007919
2017-03-14 17:36 randyarmstrong Status feedback => assigned
2017-03-16 05:40 Paul Hunkar Note Added: 0007923
2017-03-16 05:40 Paul Hunkar Status assigned => feedback
2017-03-16 09:17 randyarmstrong Note Added: 0007924
2017-03-16 09:17 randyarmstrong Status feedback => assigned
2017-03-24 03:14 Paul Hunkar Note Added: 0007958
2017-03-24 03:15 Paul Hunkar Note Added: 0007959
2017-03-24 03:15 Paul Hunkar Status assigned => resolved
2017-03-24 03:15 Paul Hunkar Resolution open => fixed
2017-04-25 20:11 Jim Luth Note Added: 0008007